Cubic 5,000ppm CO2 Sensor
The CU-1106 series of single-beam NDIR CO2 sensor modules by Cubic is designed to monitor and detect carbon dioxide levels and is ideal for providing high quality NDIR technologies for indoor air quality and HVAC applications. Simply add power and a UART signal reader like Termite to monitor CO2 levels from your PC.
Features
- Advanced NDIR Technology to improve long term stability
- High Accuracy temperature calibration within whole measurement range
- Advanced auto-calibration background
- Small, compact structure
- Easily integrated into a variety of IAQ or HVAC applications
Applications
- Indoor Air Quality
- HVAC or Demand Control Ventilation
- Automotive Cabin Air Monitoring
- Battery operated & low power applications
Models
CU-1106H-NS - 0-2,000ppm, high accuracy, footprint compatible with SenseAir S8 Commercial CO2 Sensor. Temperature calibration within whole measurement range, UART and PWM outputs.
CU-1106SL-N 0-5,000ppm, super low power version with wide voltage range designed for battery operated devices. Footprint compatible with SenseAir S11 Sunrise CO2 Sensor. Includes UART and I2C output.
CU-1106SL-NS 0-5,000ppm, super low power managed version designed for battery operated devices. Footprint compatible with SenseAir S11 Sunrise CO2 Sensor with the same UART and I2C outputs. Pin holes for flexible connections.
Models Special Order
CU-1106LS - 0-5,000ppm, ± (30ppm+3% of reading). Footprint, pin and protocol compatible with SenseAir S8 CO2 Sensor.
Specifications
Model CU-1106H-NS
- Measurement range: 0-2,000ppm PWM, 0-10,000ppm UART
- Accuracy: ± (30ppm+3% of reading) @ -10°C -50°C , 0-85%RH
- Working temperature: -10°C - 50°C
- Working humidity: 0-95%RH non-condensing
- Sampling frequency: 1 second
- Time to first reading: T90 < 30s
- Power supply: 4.5-5.5VDC
- Signal output: UART TTL, PWM linear output
- Ripple wave: <50mV
- Working current: <50mA
- Dimensions: 33x19.7x8.9mm (pins not included)
- Weight: 5g
- Storage temperature: -30°C - 70°C
- Storage humidity: 0-95%RH non-condensing
- Life span: ≥15 years
- Maintenance: Maintenance-free for normal indoor applications with Auto-calibration on
Model CU-1106SL-N
- Measurement range: 0-5,000ppm
- Accuracy: ± 50ppm+5% of reading continuous
- Accuracy: ± 50ppm+3% of reading single reading
- Working humidity: 0~95%RH non-condensing
Working current: 30uA @ 2 min measurement cycle default, 12uA @ 5 min. - Power supply: 3.3-5VDC
- Signal output: UART TTL, I2C
- Dimensions: W33*H19.7*D8.9mm (pins not included
- Weight: 5g
- Storage temperature: -30°C - 70°C
- Storage humidity: 0-95%RH non-condensing
- Installation: Waterproof breathable film upwards
Model CU-1106SL-NS
- Measurement range: 0-5,000ppm
- Accuracy: ± 50ppm+5% of reading continuous
- Accuracy: ± 50ppm+3% of reading single reading
- Working temperature: -10℃-50℃
- Working humidity: 0-95%RH non-condensing
Working current: 30uA @ 2 min measurement cycle default, 12uA @ 5 min. - Power supply: 3.3-5VDC
- Signal output: UART TTL, I2C
- Dimension: W33.5*H19.7*D9.1mm
- Weight: 5g
- Storage temperature: -30°C - 70°C
- Storage humidity: 0-95%RH non-condensing
- Installation: Waterproof breathable film upwards
Model CU-1106LS
- Measurement range: 0~5,000ppm
- Accuracy: ±50ppm+3% of reading @0℃~50℃, 50±10%RH
- Response time: ≤30s
- Working temperature: -10℃~50℃
- Working humidity: 0~95%RH non-condensing
- Power supply: 4.5V-5.5VDC
- Ripple wave: <50mV
- Working current: ≤50mA average @ 1s
- Signal output: UART TTL, PWM, I2C (reserved)
- Dimensions: W39.3*H19.7*D9.1mm
- Weight: 6g
- Storage temperature: -30°C - 70°C
- Storage humidity: 0-95%RH non-condensing
- Life span: ≥10 years
Warranty
- 90 days - See CO2Meter Terms and Conditions.