• Free ground shipping in the US • Order online • Same day shipping for products ordered by 2pm EST.

OXY-GAP Oxygen Gas Analyser Probe

OXY-GAP Oxygen Gas Analyser Probe
Regular price $3,599.00 USD

POs or wholesale quantity discounts click here

SST Sensing's OXY-GAP-100 Gas Analyzer Probe is designed to monitor the oxygen content within flue or stack gases making it a complete solution for combustion optimization and burner/boiler trim applications.

Features

  • RS485 Modbus RTU, relay, analog outputs
  • Pressure and temperature compensation
  • Sample temperatures up to 700°C
  • Operates without the need for an air reference
  • Replaceable sensor can be cleaned or replaced in seconds.
  • Calibration via fresh air or cal gas

Applications

  • Combustion control of boilers fueled by natural gas, light oil, diesel, coal and biomass
  • Excess air analysis
  • Boiler trim control
  • Incineration furnaces
  • Power generation
  • Combined cycle gas turbines (CCGT)
  • Ceramic furnace monitoring

Models

OXY-GAP-100 Gas Analyzer Probe - designed for integration in applications such as; combustion control of boilers fueled by natural gas, light oil, diesel, coal and biomass. 

Specifications

  • Measurement technology gas: Zirconium Oxide (ZrO2)
  • Measurement range: 0.1-25%
  • Output resolution: 0.01 mA or 0.01% O2
  • Accuracy: (0.1-25%): < 0.25% O2
  • Response Time (T90): < 15 seconds
  • Repeatability: < 0.25%
  • Sample Flow Effect: ±0.5% of full scale
  • Sample cell temperature: 1292°F (+700°C)
  • Temperature measurement: Pt100
  • Ambient temperature: -4 to +131°F (-20 to +55°C)
  • Ambient relative humidity: 0-95% RH
  • Background gas: Combustion gas from natural gas, bio-gas or oil 
  • Sample gas temperature: 1292°F (+700°C)
  • Sample pressure: 260-1260mbar Absolute

Electrical/Mechanical

  • Power supply: 24VDC  ±10% LPS
  • Power consumption: 700mA maximum @ 24VDC
  • Analog outputs: Single or Dual 4----20mA
  • Output ranges (oxygen): 0-25% O2
  • Output ranges (temperature): -58 to +572°F (-50 to +300°C) 
  • Output ranges (pressure): 260 - 1260mbar (0.017 - 0.086psia)
  • Warm-up time: < 90 seconds
  • Stabilization time: < 5 minutes
  • Dimensions: See Datasheet Outline Dimensions
  • Weight: Head - 3.5 lbs, Probe 8.6 lbs
  • Process connection: 2" 150 lbs ANSI flange
  • Ingress protection: IP65