Fixed Oxygen (O2) Gas Detector (0-25%)
The Fixed Oxygen (O2) Gas Detector (MSC2 + SC2-E1195-A2-P-00) is designed to protect individuals near toxic gases in commercial and industrial applications. This fixed gas safety monitor measures nitrogen, helium, oxygen (0-25%), and argon levels and detects hazards in order to protect facilities from overexposure.
Fixed oxygen gas detectors are critical in scientific, medical, industrial, manufacturing, and welding applications - or anywhere O2 is being used, stored, or produced.
Features
- Modular easy-to-use design
- 1-3 gas sensor capabilities
- 3 configurable relays
- 2 sensors max may be different sensors of the SC2 series, max 3 of them analog with 4-20 mA signals
- Custom configuration dependent upon location and application
- Warning buzzer/LED alarm, fault + operation option
- Compatible with a wide range of BMS
- Protocol for DGC-06 or Modbus protocol
- Operating voltage input 100-240 VAC or 24VDC
Specifications
- Measurement Range: 0-25%
- Gas Type: Oxygen
- Housing Type C/E: Polycarbonate
- Installation: Wall Mounted
- Knockouts for Cable Entry: Standard 6x M20/25
- Ingress Protection: IP65
-
Temperature Range: -13°F to 140°F (-30°C to 50°C)
- Humidity Range: 15-90% RH non-condensing
- Storage Temperature: -4°F to 149°F (0° to 20°C)
- Power Supply: 100-240 VAC or 24VDC
- Power Consumption: 24 V DC | Max. 60 mA (1.5 VA), w/ sensor, w/o WAO
- Alarm Relay (3): 5 A Dry Contact Configurable
- Transistor Output (2): 24 V DC/0.1 A
- Analog Input (2/3): 4-20mA, overload and short-circuit proof, input resistance 130 proportional, overload and short-circuit proof, load ≤ 500 4–20 mA = measuring range
-
Analog Output Signal (1):
- 2.4–< 4 mA = tolerable under range
- 20–21.2 mA = tolerable over range
- ≥ 21,2 mA= error over range
- ≤ 2,0 mA = fault
- Dimensions: 5.12 x 5.12 x 2.95 in. (130 x 130 x 75 mm)
- Weight: 1.32 lbs. (0.6 kg)
Warranty
- 1 year - See CO2Meter Terms and Conditions